Huadian Technology ›› 2010, Vol. 32 ›› Issue (11): 65-67.
• 技术交流 • Previous Articles Next Articles
MA Shidong
Received:
Revised:
Published:
Abstract: The variable frequency reformation of the condensate pump of 600 MW supercritical unit and its energysaving effect were analyzed. On the basis of warranty for safe operation of the condensate pump,the ‘one drive one’ mode was adopted in the variable reformation of the condensate pump. The operation data after reformation show that the reformation scheme achieves the design requirements, the power consumption of the condensate pump reduced by 36%, and the houseservice consumption rate was reduced by 0.12%, the energysaving effect is remarkable.
Key words: 600 MW supercritical steam turbine, condensate pump, variable frequency reformation, economical analysis
MA Shidong. Variable frequency reformation of condensate pump for 600 MW supercritical steam turbine[J]. Huadian Technology, 2010, 32(11): 65-67.