Huadian Technology ›› 2011, Vol. 33 ›› Issue (9): 69-71.
• 技术交流 • Previous Articles Next Articles
ZOU Qiqun, SHU Yishi, YU Peijie
Received:
Revised:
Published:
Abstract: An explosion accident of current transformer on bus coupler segment in weekinfeed side of a 220kV substation was introduced. Combining with the operation mode of the system before the accident, the phenomenon of the accident and the actions of the related protection and switches, according to the principle of the protection device, several key protection actions in the accident process were analyzed. The acting principle and acting process of the optical fiber differential protection and the optical fiber distance protection in weakinfeed line were analyzed emphatically. Combining with the characteristics of the weakinfeed line, some suggestions on its protection configuration and its secondary circuit design were put forward.
Key words: weak-infeed, substation, current transformer, explosion, protection device
ZOU Qiqun;SHU Yishi;YU Peijie. Analysis on reasons of explosion of current transformer on bus coupler segment in weakinfeed side of a substation[J]. Huadian Technology, 2011, 33(9): 69-71.