Huadian Technology ›› 2014, Vol. 36 ›› Issue (11): 20-21.
Previous Articles Next Articles
Published:
Abstract: Abstract:The author put forward runback control strategy in order to resolve soaring back pressure of the 600MW direct air cooling unit.Back pressure protection logically system of 600MW subcritical direct aircooling unit were optimized, risks of environmental strong wind may generate hot air back flow above air cooling island and with soaring back pressure, direct aircooling unit may trip were reduced. In this way, the unit safe operation under hostile circumstances of high back pressure were ensured.
Key words: Keywords:direct air cooling unit, back pressure soaring, runback, logical optimization
WANG Tiankun. The logical optimization for the soaring back pressure protection of 600MW direct air cooling unit[J]. Huadian Technology, 2014, 36(11): 20-21.