Abstract:
Abstract:In order to solve the blocking and failure problems of the demister of wet flue gas desulfurization system of a 600MW units, the twolayer flat plate type demister was reformed into onestage tubular plus twostage roof type demister. The reformation scheme, the construction period, the project cost and the test result were introduced in detail. After the reformation, the liquid drop content of the flue gas in absorption tower outlet was reduced effectively, and safe operation of the unit and desulphurization system was ensured.
Key words: Keywords:600MW unit, wet flue gas desulphurization, demister, analysis on reformation
NIE Pengfei. Analysis on reformation of wet desulphurization demister of a 600MW unit[J]. Huadian Technology, 2015, 37(8): 70-71.