  1. Huadian Laizhou Power Generation Company Limited, Laizhou 261441, China
  • Online:2016-06-25 Published:2016-09-21

Abstract:

Abstract:After analyzed the incident of Huadian Laizhou Power Generation Company Limited 1000MW ultra critical unit steam turbine A transformer trip,the author indicated that the transformer low voltage side outlet busbar is too close to power distribution cabinet,and caused flashover and A transformer protection trip. Treatment measurements and matters need attention while power recovery was indicated. 