Vietnam Duyen Hai 3 Thermal Power Plant unit No.1 vibration analysis and treatment

  

  1. China Chengda Engineering Company Limited, Chengdu 610041, China
  • Published:2017-08-25

Abstract:

The generating unit of Vietnam Duyen Hai 3 Thermal Power Plant was overvibrating in noload and normal operating condition. Especially in generator temperaturerise test, the vibration value varied with variation of exciting value. After analysis, unit vibration was mainly caused by rotor imbalance. By site balance adjustment, the problem of overvibration was effectively solved.