Huadian Technology ›› 2019, Vol. 41 ›› Issue (6): 23-26.

Previous Articles     Next Articles

Analysis of an abnormal alarm of TV for a 220kV main transformer protection

  

  1. 1.a.School of Electrical and Information Engineering; b.Institute of Engineering Technology, Hubei University of Science and Technology, Xianning 437000, China; 3.State Grid Changde Power Supply Company, Changde 415000, China
  • Published:2019-06-25

Abstract:

Taking an abnormal alarm of TV for a 220kV main transformer protection as an example, it is found that excessive third harmonic is a cause for abnomal TV.Furthermore,when a harmonic elimination is equipped at the TV neutral point, it can produce voltage and third harmonics in the zero sequence opendelta connection, causing abnormal alarm of TV for  main transformer protection.Corresponding methods are put forward to ensure the safe and stable operation of the main equipment of substation.