Huadian Technology ›› 2011, Vol. 33 ›› Issue (3): 16-19.
• 研究与开发 • Previous Articles Next Articles
PAN Wenrui, REN Jianxing, WENG Jianhua, ZENG Xianping
Received:
Revised:
Published:
Abstract: The circulating water temperature is an important index for ensuring good vacuum of condenser and reducing the energy consumption of unit. If the circulating water temperature decreased by 1℃, the vacuum of the condenser would increase by 400~500Pa, and the unit coal consumption would decrease by 1.0~1.5g/(kW·h). As an important equipment of circulating cooling system in thermal power plant, the cooling effect of cooling tower is the key factor influencing on circulating water temperature. Based on the consideration of enhancing the cooling effect of cooling tower, taking the hyperbolic wet cooling tower with natural convection in 300MW thermal power plant as prototype, a simulating test device for circulating cooling system was designed and built. The calculation of aerodynamic characteristics for the model tower was carried out to realize the purpose of simulating the internal flow of the cooling tower and evaluating the cooling effect in 300MW thermal power plant to some extent.
Key words: thermal power plant, cooling tower, modeling, aerodynamic characteristics calculation
PAN Wenrui;REN Jianxing;WENG Jianhua;ZENG Xianping. Modeling and aerodynamic characteristics calculation of circulating water cooling tower in 300MW thermal power plant[J]. Huadian Technology, 2011, 33(3): 16-19.
/ Recommend
Add to citation manager EndNote|Ris|BibTeX
URL: https://www.hdpower.net/EN/
https://www.hdpower.net/EN/Y2011/V33/I3/16
Fault analysis on desulfurization DCS signal interference in a thermal power plant
Quality evaluation and performance analysis of WC9 cast steel safety valve for inservice units in a thermal power plant
Experimental study on electrochemical technology for circulating water treatment in thermal power plant