Huadian Technology ›› 2012, Vol. 34 ›› Issue (10): 64-65.
• 技术交流 • Previous Articles Next Articles
WANG Hui
Received:
Revised:
Online:
Published:
Abstract:
The working principle of the vacuum oil filter was introduced. The reason of frequent fault of vacuum fireresistant oil filter in Guangdong Datang
International Chaozhou Power Generation Company Limited was analyzed.The main reason of the oil filter fault was determined that the lower temperature of the
fireresistant oil, which causes the viscosity of the fireresistant oil to increase. The viscositytemperature characteristics of the fireresistant oil
can influence on the system equipments more greatly,and the operators must adjust the oil temperature in accordance with the site environmental temperature
to ensure the system equipments to operate in best working state.
Key words: fire-resistant oil, vacuum oil filter, fault, viscosity
WANG Hui. Analysis on reason of fault of fireresistant oil filter[J]. Huadian Technology, 2012, 34(10): 64-65.
0 / / Recommend
Add to citation manager EndNote|Ris|BibTeX
URL: https://www.hdpower.net/EN/
https://www.hdpower.net/EN/Y2012/V34/I10/64
Fault recovery strategy for distribution network with isolated island and reconfiguration
Fault analysis on desulfurization DCS signal interference in a thermal power plant
Identification method and software design of testing failure report based on fault information system