华电技术 ›› 2011, Vol. 33 ›› Issue (11): 15-16.

• 研究与开发 • 上一篇    下一篇

大型发电机组过励磁保护整定计算

范宇豪   

  1. 湖北西塞山发电有限公司,湖北黄石435000
  • 收稿日期:1900-01-01 修回日期:1900-01-01 出版日期:2011-11-25 发布日期:2011-11-25

Setting calculation of overexcitation protection for large generator set

FAN Yuhao   

  1. Hubei Xisaishan Power Generation Corporation Limited, Huangshi 435000, China
  • Received:1900-01-01 Revised:1900-01-01 Online:2011-11-25 Published:2011-11-25

摘要: 发电机变压器组过励磁保护应根据发电机、变压器允许过励磁的耐受能力进行整定计算,其定值还应与励磁系统U*-f*限制曲线配合,按发电机励磁调节器U*-f*限制元件的后备保护整定。通过对湖北西塞山发电有限公司680MW机组发电机、变压器过励磁曲线和ABB励磁系统U*-f*限制曲线的分析,对过励磁保护动作值和动作时间进行了具体分析和计算。

关键词: 过励磁曲线, U*-f*限制曲线, 配合, 分析

Abstract: The setting calculation of the overexcitation protection for generatortransformer unit must be based on the tolerance of the generator and the transformer to the overexcitation. The settings must be matched up with U*-f* limit curve of the excitation system; it must be adjusted in accordance with the backup protection of U*-f* limit component of generator field regulator. According to the analyses of overexcitation curve of the 680MW generator and transformer in Hubei Xisaishan Power Generation Corporation Limited and the U*-f* limit curve of ABB excitation system, the responding value of overexcitation protection and the actuation time were analyzed and calculated concretely.

Key words: over-excitation curve, U*-f* limit curve, match up, analysis