华电技术 ›› 2012, Vol. 34 ›› Issue (8): 54-56.

• 技术交流 • 上一篇    下一篇

300MW机组风机变频控制系统研究与改进

郑伟   

  1. 天津华能杨柳青热电有限责任公司,天津300380
  • 收稿日期:1900-01-01 修回日期:1900-01-01 出版日期:2012-08-25 发布日期:2012-08-25

Research and improvement of variable frequency control system for draught fans of 300MW unit

ZHENG Wei   

  1. Tianjin Huaneng Yangliuqing Thermal Power Company Limited, Tianjin 300380, China
  • Received:1900-01-01 Revised:1900-01-01 Online:2012-08-25 Published:2012-08-25

摘要:

以天津华能杨柳青热电有限责任公司300MW机组引风机为例,介绍了引风机变频控制系统改造后自动控制系统的相关逻辑和功能,针对变频器调节速度快、2台引风机1台工

频运行1台变频运行时自动平衡及纠偏等问题,采取了更换入口挡板调节电动执行机构、调整PID调节器参数、增加2台引风机自动平衡及纠偏逻辑等措施。静、动态试验和实际运行

证明,对引风机变频控制系统的优化改进达到了预期目标,机组引风机的运行更加经济、可靠。

关键词: 发电厂, 风机变频, 自动平衡, 纠偏, 控制系统, 节能减排

Abstract:

Taking the induced draught fans of the 300MW unit in Tianjin Huaneng Yangliuqing Thermal Power Company Limited as example, the relative logic and

functions of the automatic control system after reformation of variable frequency control system for the induced draught fans were introduced. Some problems

were existed in the variable frequency control system, which including that the adjustment speed of the frequency converter is faster than electric actuator

of the fan inlet damper adjustor, and when one of the two fans is driven by frequency converter and the other is driven by 50Hz power source, there are not

automatic balancing and deviation rectification functions in the original control system. In order to solve above problems, the electric actuator of the fan

inlet damper adjustor was replaced, the parameters of the PID adjustor were adjusted, and the two fans automatic balancing function and deviation

rectification logic were added into the system. The static and dynamic tests and practical operation show that the improvement of the variable frequency

control system achieves expect goal, the induced draught fans operate more economically and reliably.

Key words: power plant, variable frequency controlled fan, automatic balance, deviation rectification, control system, energy saving and emission reduction