600MW发电机定子线棒层间温度高的原因分析及处理措施

  

  1. (广东珠海金湾发电有限公司,广东珠海〓519000)
  • 出版日期:2013-07-25 发布日期:2013-08-20

Analysis on higher interlayertemperature of stator coil bar of 600MW generator and treatment measures

  1. (Guangdong Zhuhai Jinwan Power Generation Company Limited, Zhuhai 519000, China)
  • Online:2013-07-25 Published:2013-08-20

摘要:

摘要:介绍了一起大型汽轮发电机定子线棒层间温度高的故障,通过分析得出层间温度高的原因是定子线棒出现堵塞。分析了堵塞物的成分和堵塞原因,提出了定冷水系统清洗的方法,清洗后各线棒层间温度最大偏差为2℃,故障消除。

关键词: 关键词:汽轮发电机, 定子线棒, 温度, 堵塞, 化学清洗

Abstract:

Abstract:A higher interlayertemperature fault of stator coil bar of a large turbogenerator was introduced. It was found by analysis that the reason of higher interlayertemperature is the blockage of the stator coil bar. The composition of the blockages and the reason of the blockage were analyzed. The method to clean the stator cooling water system was put forward. After cleaning, the maximum deviation of the interlayertemperature is 2℃, and the fault was eliminated.

Key words: Key words:turbogenerator, stator coil bar, temperature, blockage, chemical cleaning