AP1000核电机组发电机及变压器差动保护校验方案

  

  1. (三门核电有限公司,浙江三门〓317112)
  • 出版日期:2014-04-25 发布日期:2014-06-16

Test program of differential protection for generator and transformer of AP1000 nuclear power unit

  1. (Sanmen Nuclear Power Company Limited, Sanmen 317112, China)
  • Online:2014-04-25 Published:2014-06-16

摘要: 摘要:以三门核电有限公司 #1机组为背景,提出了AP1000核电机组发电机及变压器差动保护的校验方案。因主变压器受电初期厂内负荷容量的限制,建议利用中压电动机启动电流校验差动保护的正确性。为达到试验要求,将厂用变压器厂压侧电流互感器与发电机出口断路器内的电流互感器进行了比较。通过计算和对比,验证了方案的合理性。

关键词: 关键词:AP1000核电机组, 变压器, 发电机, 差动保护, 校验, 电流互感器

Abstract: Abstract:Taking the unit No.1 of Sanmen Nuclear Power Company Limited as background, a test program of differential protection for generator and transformer of AP1000 unclear power unit was proposed. Considering that the current of the main transformer is limited by the load of the plant in preliminary stage, the suggested solution is to use the starting current of the mediumvoltage motor to test the correctness of the differential protection. In order to satisfy the test requirement, the current transformer in high voltage side of the house service transformer was compared with the current transformer in outlet of the generator (the generator outlet breaker is included). The rationality of the test program was verified by the calculation and comparison.

Key words: Keywords:AP1000 nuclear power unit, transformer, generator, differential protection, test, current transformer