Huadian Technology ›› 2013, Vol. 35 ›› Issue (5): 29-32.
• 技术交流 • Previous Articles Next Articles
DAI Xihui
Received:
Revised:
Online:
Published:
Abstract: In test of valve movability of steam turbine DEH control system, after the mediumpressure regulating valve had been opened, the valve closed off incorrectly by itself. The reason of the fault was analyzed. It was found by inspection that the logic of the test of valve movability of steam turbine DEH control system is irrational. The logic optimization scheme was proposed, which makes the logic of the valve movability test for the steam turbine DEH system to be more rigorous.
Key words: steam turbine digital electro-hydraulic control system (DEH), test of valve movability, medium-pressure regulating valve, fault, reason analysis, logic optimization
DAI Xihui. Analysis on reason causing mediumpressure regulating valve to close off incorrectly by itself[J]. Huadian Technology, 2013, 35(5): 29-32.