Analysis on higher interlayertemperature of stator coil bar of 600MW generator and treatment measures

  

  1. (Guangdong Zhuhai Jinwan Power Generation Company Limited, Zhuhai 519000, China)
  • Online:2013-07-25 Published:2013-08-20

Abstract:

Abstract:A higher interlayertemperature fault of stator coil bar of a large turbogenerator was introduced. It was found by analysis that the reason of higher interlayertemperature is the blockage of the stator coil bar. The composition of the blockages and the reason of the blockage were analyzed. The method to clean the stator cooling water system was put forward. After cleaning, the maximum deviation of the interlayertemperature is 2℃, and the fault was eliminated.

Key words: Key words:turbogenerator, stator coil bar, temperature, blockage, chemical cleaning