Analysis of abnormal occurrence of WDPF system manual operation station

YAO Xiujuan, LIU San, HE Hui   

  1. Huadian International Zouxian Power Plant, Zoucheng 273522, China
  • Received:1900-01-01 Revised:1900-01-01 Online:2011-01-25 Published:2011-01-25

Abstract: Since the WDPFII distributed control system of Huadian International Zouxian Power Plant had been put into operation, the MA station was switched over from AUTO mode into LOCAL mode many times. It was decided by analysis that the abnormal occurrence is caused due to that the output frequency of the UPS, which supplies power for the WDPF system, was varied rapidly. It is desired that the result can be used as reference for fault analysis of similar DCS system.

Key words: WDPF system, manual operation station (MA station), uninterruptible power supply (UPS), frequency