Influence of line fault reclosing on transformer differential protection

PENG Peng1, LIANG Wei1, YIN Cong2, LU Zhigang3   

  1. 1.Huadian Guizhou Wujiangdu Power Plant, Zunyi 563104, China; 2.Guizhou Electric Power Dispatch and Communication Bureau, Guiyang 550002, China; 3.Electric Engineering School of Guizhou University, Guiyang 550025, China
  • Received:1900-01-01 Revised:1900-01-01 Published:2010-05-25

Abstract: The shortline fault was occurred in transformer No.0 of Wujiangdu Power Plant. After the fault was cleared, the line protection was reclosed into the fault point. The reason, which caused the transformer differential protection to act, was analyzed. The analysis shows that in certain reclose time, when the shortline fault occurred, the transformer differential protection could act in certain probability. The relevant solving measures were put forward.

Key words: reclose, transformer differential protection, act